Miniature automatic circuit breaker from the Acti9 NG125H range, designed to protect electrical circuits in installations in small buildings and small businesses. Features thermal-magnetic technology with C curve, ensuring protection against overloads and short circuits.
Technical Features
- Number of poles: 2P
- Number of protected poles: 2
- Rated current [In]: 16 A at 40 °C
- Network type: AC
- Tripping curve: C
- Breaking capacity code: H
- Ultimate breaking capacity [Icu]: 36 kA at 380...415 V AC 50/60 Hz
- Service breaking capacity [Ics]: 22,5 kA 75 % according to Icu - 380...415 V AC 50/60 Hz
- Rated operating voltage [Ue]: 220...240 V AC 50/60 Hz, 380...415 V AC 50/60 Hz, 440 V AC 50/60 Hz, 500 V AC 50/60 Hz, <= 250 V DC
- Rated insulation voltage [Ui]: 690 V AC 50/60 Hz
- Surge voltage withstand [Uimp]: 8 kV according to Icu
- Magnetic trip limit: 8 x In +/- 20%
- Contact position indicator: Yes
- Local indicators: Trip indicator, On/Off indication
- Mounting: Adjustable clip, symmetrical 35 mm DIN rail mounting support
- Step size: 9 mm
- Dimensions: 103 mm (height), 54 mm (width), 81 mm (depth)
- Weight: 0.48 kg
- Mechanical durability: 20000 cycles
- Electrical durability: 10000 cycles
- Lockable: With lock, description: Integrated lock
- Connections: Tunnel-type terminals 1.5…50 mm² rigid, 1…35 mm² flexible
- Stripping length: 20 mm
- Tightening torque: 3.5 N·m
- Earth leakage protection: Independent lock
- Protection degree IP: IP20 according to IEC 60947-2
- Impact protection degree IK: IK05 according to EN/IEC 62263
- Contamination degree: 3 according to IEC 60664-1
- Overvoltage category: IV
- Tropicalization: 2 according to IEC 60068-1
- Relative humidity: 95 % at 55 °C
- Operating ambient temperature: -30…70 °C
- Storage ambient temperature: -40…70 °C
- Standards: IEC 60947-2
- Sustainable offering status: Green Premium product
- Compliant with REACh without SVHC: Yes
- EU RoHS Directive: Compliant
- Free of toxic heavy metals: Yes
- Mercury-free: Yes
- RoHS exemption information: Yes
- China RoHS regulation: Proactive China RoHS declaration (outside legal scope of China RoHS)
- WEEE: In the European Union market, the product must be disposed of according to a specific waste collection system and never end up in a regular trash container