4-pole DPX³ 160 MCCB, designed to protect electrical circuits against overloads and short circuits in medium-voltage installations. This molded case device offers a robust and reliable solution for current control and safety in industrial and commercial environments.
Technical features
- Rated permanent current (Iu): 160 A.
- Rated voltage range: 220...690 V.
- Breaking capacity (Icu) at 400 V, 50 Hz: 16 kA.
- Overload protection range adjustment: 128...160 A.
- Construction: Fixed integrated technology for integrated device.
- Main circuit connection type: Threaded connection.
- Compatible with symmetrical DIN rail mounting.
- Optional DIN rail mounting with top guide.
- Includes 1 normally closed auxiliary contact and 1 changeover contact.
- Disconnection indicator available.
- Integrated undervoltage release.
- Control element: Handle.
- Protection rating: IP30.
The fixed configuration and threaded connections ensure a stable and secure installation. The availability of auxiliary contacts and the undervoltage release facilitates integration into control and automation systems, allowing efficient management of the switch status.