Miniature automatic circuit breaker from the Acti9 NG125L range, designed to protect electrical circuits in installations in small buildings and small businesses. Offers thermal and magnetic protection with C curve, suitable for nominal currents of 32 A at 40 °C, and supports high breaking capacities at various AC and DC voltages.
Technical Features
- Number of poles: 2P
- Number of protected poles: 2
- Neutral position: Left
- Rated current [In]: 32 A at 40 °C
- Network type: AC, DC
- Trip unit technology: Thermal-magnetic
- Curve code: C
- Breaking capacity code: L
- Breaking capacity [Icu]: 100 kA (220...240 V AC 50/60 Hz), 40 kA (440 V AC 50/60 Hz), 50 kA (380...415 V AC 50/60 Hz), 15 kA (500 V AC 50/60 Hz), 36 kA (≤ 250 V DC)
- Service breaking capacity [Ics]: 75 kA (75% of Icu at 220...240 V AC), 37.5 kA (75% of Icu at 380...415 V AC), 30 kA (75% of Icu at 440 V AC), 11.25 kA (75% of Icu at 500 V AC), 50 kA (100% of Icu at ≤ 250 V DC)
- Rated operating voltage [Ue]: 220...240 V AC, 380...415 V AC, 440 V AC, 500 V AC, ≤ 250 V DC
- Rated insulation voltage [Ui]: 690 V AC 50/60 Hz
- Surge voltage withstand [Uimp]: 8 kV
- Magnetic trip limit: 8 x In ± 20%
- Application category: Category A
- Switching capability: Yes
- Supply frequency: 50/60 Hz
- Position indicator: Yes
- Local indicators: On/off indication, trip indicator
- Control type: Handle, manual trip test
- Mounting type: Adjustable clip
- Mounting support: Symmetrical 35 mm DIN rail
- Compatibility with distribution block and busbar comb type: Yes
- Spacing: 9 mm, 6 steps
- Height: 103 mm
- Width: 54 mm
- Depth: 81 mm
- Weight: 0.48 kg
- Mechanical durability: 20000 cycles
- Electrical durability: 10000 cycles
- Lockable: With lock
- Locking options: Integrated lock
- Connections - terminals: Tunnel-type terminals (1.5…50 mm² rigid, 1…35 mm² flexible)
- Stripping length: 20 mm
- Torque: 3.5 N·m
- Earth leakage protection: Independent block
- Compatibility code: NG125
- Protection degree IP: IP20
- Impact protection degree IK: IK05
- Contamination degree: 3
- Overvoltage category: IV
- Tropicalization: 2
- Relative humidity: 95 % at 55 °C
- Maximum operating altitude: 2000 m
- Operating ambient temperature: -30…70 °C
- Storage ambient temperature: -40…70 °C
- Standards: Icu
- Sustainable offering status: Green Premium product
- Compliant with REACh without SVHC: Yes
- EU RoHS Directive: Compliant
- Free of toxic heavy metals: Yes
- Mercury-free: Yes
- RoHS exemptions information: Yes
- China RoHS regulation: Proactive China RoHS declaration
- WEEE: Must be disposed of according to specific collection system in the EU